H3G-TA Remote Data Center Intelligent Online Monitor Internal Resistance Battery Temperature Monitoring System For Lead Acid

FOB Reference Price:Get Latest Price
$50.00 - $80.00 / Unit | 1 Unit/Units (Min. Order)
Type:
battery monitoring system
Style:
BMS
Channels:
support Modbus/RTU/ Modbus/TCP/SNMP protocol and has dry contact output
Lead Time:
Quantity(Units) 1 - 100 >100
Est. Time(days) 7 Negotiable
Customization:
Customized logo (Min. Order: 1000 Units)
Report Suspicious Activity
Overview
Quick Details
Place of Origin:
Zhejiang, China
Brand Name:
HUASU
Model Number:
H3G-TA-13
Battery Type:
1.2V/2V/6V12V Battery System
BMS Type:
Wiring System
Monitoring Contents1:
Battery Voltage/Internal Resistance/Internal Temperature
Monitoring Contents2:
/Battery String Current/Voltage/Ambient Temperature
Used For:
1.2V, 2V, 6V or 12V battery
Certification:
ISO9001/CE/ROHS/UL/EMC/SGS
Application:
UPS/Data Center/Telecommunications/Fire&Safety System/Metro
Environmental:
Operating Temperature:-5℃~50℃,5%~90%RH
Detecting parameter:
Battery Voltage, Electricity, Resistance, Temperature
Batter Monitor Unit Software:
With HUASU Online Monitoring Software
Supply Ability
Supply Ability:
100000 Piece/Pieces per Month
Packaging & Delivery
Packaging Details
Standard export packing for HUASU Battery monitoring system
Port
Ningbo, Shenzhen, Hangzhou, Shanghai
Picture Example:
package-img
Lead Time :
Quantity(Units) 1 - 100 >100
Est. Time(days) 7 To be negotiated
Video Description
Product Description

   Our CELLCHECK intelligent battery monitor is designed special for single cell monitoring. It combines advanced technology with patented hardware for the most thorough stationary battery health analysis in the industry. The module can be pasted on the monitored battery's case directly or mounted an additional rail.

Product Name
H3G-TA Battery Monitoring System
Battery Type
1.2V, 2V, 6V,12V Battery Voltage
Used For
Lead Acid, Lithium Battery, Nickel Battery
Monitoring Parameter
Battery voltage, internal resistance, internal temperature, battery string current, voltage, ambient temperature

Power Requirements
CELLCHECK:powered from the battery, less than 60mA(2V) or 25mA(12V)
CM module:85~264VAC,100V~370VDC,15W
TC module:DC8~13V,2W
Communications Interfaces
TA Module:UART port, meet MODBUS protocolConverter
CM module:RS485, Ethernet Port , meet MODBUS/RTU,MODBUS/TCP and SNMP protocol
TC module:UART port, meet MODBUS protocol
Environmental
Storage temperature: -10℃~70℃,5%~90%RH
Operating temperature:-5℃~50℃,5%~90%RH
Application
Datacenter/Nuclear Power Station/Electric Substation/Bank/Base Station/Transportation, etc.


BMS Components

Overview

• Continuous 24/7 on-line monitoring
• One CELLCHECK monitor one cell, including battery internal resistance, voltage and temperature 
• Software is available to collect data from CELLCHECK
• Serial port with Optical isolation, meet MODBUS protocol, easy to be accessed by UPS controller
• Easy to install without specialized training


UL VW-1 Test Method


All cables including voltage collecting cable, internal testing cable and other conneting cables are all flame retardant lines, and are in compliance with the fire retardant requirements specified in the UL VW-1 and GBT 18380.1 standard.





Packaging & Delivery


Standard Export Carton

Normal Size: 52.3*33.8*19.5




Main Products

Related Product
Application & Cases

• IT Enterprise &Data center
• Telecommunications
• Battery supplied applications
• Utilities 
• Fire &Safety system
• Remote monitoring

• Base Station

• UPS System

• Nuclear Power Station

• Electric Subsation

• Bank

• Transportation

• Government

Project Cases

User Name                                               Battery Situation                                                              Installation Site

Our Partner
About US

At HUASU battery monitoring and management is all we do. We keep on researching it intimately, so you don't have to. Our company was established on year 2003, 4 generations (2V &12V concentrated system, cellcheck system, wireless system) BMS has been developed. 


We provide BMS products and related services to the world, such as Schneider, Eaton, Emerson, etc. We also are the qualified supplier of ZTE, Delta and Huawei.


Profession, specialty, refinement and particularity have been the keys to HUASU's success.

Contact us

Factory Add:No.16, Road 5th of Xiyuan, Xihu Tech-economy Zone, Hangzhou, China

Tel:+86-571-86693075

Fax:+86-571-87968969
Skype: huasu.joanna
Mob/WeChat/WhatsApp:18324428238
Website:http://www.huasucn.com/En/indexEn.html

Our Team

Our Certificates

             ROHS                        CE(EMC)                         UL                                    CE                           ISO9001

Produce Line
FAQ

Q1. Why monitoring battery internal Resistance?

A:  Generally, we confirm the battery situation through discharging of the battery. With this handling, we can work on the real capacity but it is very time-consuming. After doing reasearchs, we find the internal resistance of the battery will be increased that due to various causes of capacity decline. If we regularly monitor the internal resistance of the battery and compare it with the initial internal resistance, it will be easy to detect the performance change of the battery and also find out the problem battery. 

Q2. Why monitoring battery temperature?

A:  Battery temperature is like human body temperature, when there is a problem with the battery internal temperature will tend to rise, generally like the battery internal part of short circuit, charging voltage is too high will cause temperature rise. Therefore, the problem of battery pack can be detected as early as possible by monitoring the temperature inside the cell.

Q3. Can your products be discharged remotely?

A:  Yes, the control unit can be controlled remotely, and the capacity unit can be controlled by the control unit to discharge the battery. But when discharging, the battery pack needs to be operated manually or other control methods to separate from the power supply system. We have done the whole system including the charger by technology project of remote control, but this method is not promotion, mainly is the present charger stability DC screen is not enough, manufacturers can not guarantee the safety and effectiveness of the remote control function, easily lead to loss of control. At present, the technology of remote discharge products in the market is not mature, as a pilot can, it is not suitable to promote, it is recommended that users do not use this product at present.

Q4. Do your products have the balance function?

A:  Yes. We take the method of shallow charge & discharge for the battery to the battery voltage balance section.

Q5. How does the product solve the line interference and the environmental interference ?

A:  We have considered various interference conditions during the design , and special EMC is processing on the circuit which can meet the requirements specified in UL and DL / T856 - 2004 , and we have corresponding EMC test reports.

Q6. The equipment can access to the third party system? How to access?

A:  Yes. It is very easily access to your third party system. Generally, you only take one or two days to put programs.H3G system comes with a special serial port for the use of third party system, support the MODBUS protocol. The specific access method and communication protocol can be provided by our customer service department.